Inspection History: PLUMBING - PRE SLAB

Permit Number - T07CM00244

Inspection Description - PLUMBING - PRE SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2007 PLUMBING - PRE SLAB Approved IVRS - Inspection :*
05/29/2007 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
TOILET RMS. OK FOR CONCRETE
05/24/2007 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1. ROUGH PLUMBING W/TEST TO ABOVE FIXTURE FITTINGS OK TO BACKFILL.
2. RECALL PRIOR TO CONCRETE
3. 2" K WATER LINE W/BRAZED JOINT & 100 PSI TEST INSTALLED FROM EXISTING SERVICE LOCATION TO NEW METER LOCATION.
4. PROVIDE PERM PIPE PLUGS IN ALL DEMO PIPING. CALL FOR INSP.
5. REMOVE DEMO VENTS THROUGH ROOF. PIPING STILL IN PLACE PRESENTS A HAZARD.
05/22/2007 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
CORRECT BACK SLOPE AT 4" WYE, AND AT TRAP ARM
OK TO COVER EAST OF TIE IN POINT.
05/21/2007 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
1. NOT INSTALLED PER PLAN
2. NO REDLINES ON SITE
3. WILL REQUIRE FULL SIZE CLEANOUT ON ALL BRANCH PIPING OVER FIVE FEET FROM MAIN
4. WET VENT FOR URINAL TO BE ONE PIPE SIZE LARGER THAN REQUIRED WASTE FOR URINAL.