Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PRE SLAB
Permit Number - T07CM00244
Inspection Description - PLUMBING - PRE SLAB
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | PLUMBING - PRE SLAB | Approved | IVRS - Inspection :* | |
| 05/29/2007 | PLUMBING - PRE SLAB | Partial Approval | IVRS - Inspection :* TOILET RMS. OK FOR CONCRETE |
|
| 05/24/2007 | PLUMBING - PRE SLAB | Partial Approval | IVRS - Inspection :* 1. ROUGH PLUMBING W/TEST TO ABOVE FIXTURE FITTINGS OK TO BACKFILL. 2. RECALL PRIOR TO CONCRETE 3. 2" K WATER LINE W/BRAZED JOINT & 100 PSI TEST INSTALLED FROM EXISTING SERVICE LOCATION TO NEW METER LOCATION. 4. PROVIDE PERM PIPE PLUGS IN ALL DEMO PIPING. CALL FOR INSP. 5. REMOVE DEMO VENTS THROUGH ROOF. PIPING STILL IN PLACE PRESENTS A HAZARD. |
|
| 05/22/2007 | PLUMBING - PRE SLAB | Partial Approval | IVRS - Inspection :* CORRECT BACK SLOPE AT 4" WYE, AND AT TRAP ARM OK TO COVER EAST OF TIE IN POINT. |
|
| 05/21/2007 | PLUMBING - PRE SLAB | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN 2. NO REDLINES ON SITE 3. WILL REQUIRE FULL SIZE CLEANOUT ON ALL BRANCH PIPING OVER FIVE FEET FROM MAIN 4. WET VENT FOR URINAL TO BE ONE PIPE SIZE LARGER THAN REQUIRED WASTE FOR URINAL. |