Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00244
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* FINISH SUPPORTING M/C, FLEX & VDV CABLES & CONDUITS AS PER CODES 725.6, 800.6, 815.6 & 300.11 |
|
| 07/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK 1G PANEL & CASH WRAPS 1. FINISH SUPPORTING VDV CABLES 6' & BOTH END NOT OFF OF CONDUIT 2. FINISH SUPPORTING M/C CABLES & FLEX BOTH END - NOT OFF OF CONDUIT 3. CORDS NOT ALLOWED ABOVE CEILING - 400.7 & 8 4. OPEN SHELVING LIGHTS AS DISCUSSED 5. FINISH T-STATS ON POLES |
|
| 07/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. FINISH AC'S 2. GFCI NOT WORKING BUILDING: 1. FINISH VDV 2. FINISH ISO GROUND 3. FINISH CASH WRAPS 4. EM LIGHTS & EXITS TO BE AS PER 700.12 |
|
| 07/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CASH WRAPS: 1. SUPPORT POWER POLES 2. SUPPORT VDV CABELING 725.6 & 800.6 3. USE APPROVED WIRING METHODS FOR 1.G CIRCUITS 4. GROUND JUNCTION BOXES 5. FINISH MAKE UP IN CEILING 1) GROUND FIRE ALARM PANELS 2) FILL UNUSED OPENING IN GUTTER & PANEL ROOF 1. USE APPROVED MC FITTINGS - ALSO BROKEN SHEATH 2. SUPPORT BOXES OVER 1' IN AIR 3. TIGHTEN LOOSE FITTINGS & PROPERLY SUPPORT CARFLEX/SEALTITE 4. ISOLATE PRIMARY POWER IN A/C UNITS BUILDING 3. LABEL DISCONNECTS 4. BOND AT CONCENTRICS 250.97 5. BOXES AT COMBUSTIBLES & MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 |