Permit: T07CM00244

Parcel: 12105021A


Addresses:

5550 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00244

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
FINISH SUPPORTING M/C, FLEX & VDV CABLES & CONDUITS AS PER CODES 725.6, 800.6, 815.6 & 300.11
07/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK 1G PANEL & CASH WRAPS
1. FINISH SUPPORTING VDV CABLES 6' & BOTH END
NOT OFF OF CONDUIT
2. FINISH SUPPORTING M/C CABLES & FLEX
BOTH END - NOT OFF OF CONDUIT
3. CORDS NOT ALLOWED ABOVE CEILING - 400.7 & 8
4. OPEN SHELVING LIGHTS AS DISCUSSED
5. FINISH T-STATS ON POLES
07/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. FINISH AC'S
2. GFCI NOT WORKING

BUILDING:
1. FINISH VDV
2. FINISH ISO GROUND
3. FINISH CASH WRAPS
4. EM LIGHTS & EXITS TO BE AS PER 700.12
07/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CASH WRAPS:
1. SUPPORT POWER POLES
2. SUPPORT VDV CABELING 725.6 & 800.6
3. USE APPROVED WIRING METHODS FOR 1.G CIRCUITS
4. GROUND JUNCTION BOXES
5. FINISH MAKE UP IN CEILING

1) GROUND FIRE ALARM PANELS
2) FILL UNUSED OPENING IN GUTTER & PANEL

ROOF
1. USE APPROVED MC FITTINGS - ALSO BROKEN SHEATH
2. SUPPORT BOXES OVER 1' IN AIR
3. TIGHTEN LOOSE FITTINGS & PROPERLY SUPPORT CARFLEX/SEALTITE
4. ISOLATE PRIMARY POWER IN A/C UNITS

BUILDING
3. LABEL DISCONNECTS
4. BOND AT CONCENTRICS 250.97
5. BOXES AT COMBUSTIBLES & MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20