Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T07CM00244
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 06/25/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) A BOND IS TO BE POSTED FOR TEMP POWER FOR TEST |
|
| 06/22/2007 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1. MOVE GROUNDING ELECTRODE CONDUCTOR TO 1ST DISCONNECT AND ACCESSIBLE 2. BONDING JUMPERS TO BE SIZED PER 250.66 (LINE) & 250.122 (LOAD) 3. NEED REJECTION PINS 4. LABEL DISCONNECT 5. TRANSFORMER GROUNDING ELECTRODE CONDUCTOR TO FOLLOW CODE ORDER 250.30(A)(7) 6. BOND WATER TO INTERIOR SIDE 7. FINISH CEILING |