Permit: T07CM00229

Parcel: 123052860


Addresses:

2350 E JUANITA ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/31/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/29/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED SPECIFIC DETAILS ON HOW #1 & #2 BELOW IS BEING COMPLIED WITH
05/21/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNTIL 13 1/2 X 4 1/2 GLU LAM IS SUPPORTED PERMANENTLY AND TRUSS GIRDERS AT KITCHEN ARE SUPPORTED
2) DRAWINGS DON'T SHOW HOW TRUSS GIRDER WILL BE SUPPORTED. NEED SOMETHING TO GO BY.L FRAMING OF BEARING WALL
4) GLU LAM NEEDS TO BE STRAPED AT BOTH ENDS WITH ST9 STRAP
5) IF YOU WISH TO DRY IN ROOF-PROCEED AT YOUR OWN RISK
05/16/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WALKED ROOF-EVERYTHING OK, BUT DO NOT LOAD UNTIL HEADERS ARE FIXED AT DOOR OPENINGS
2) MISSING CROSS BRACING GABLE ENDS
3) HEADERS AT DOOR OPENING NOT PER FRAMING PLAN