Permit: T07CM00222

Parcel: 138230850

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/29/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/28/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
03/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/21/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/13/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) ITEMS 1-6 TO BE CORRECTED AS SOON AS POSSIBLE-RELEASED ONLY BECAUSE OCCUPIED
2) PLASTIC ANCHORS NOT ALLOWED ON SERVICE RISERS
3) ADDRESS SERVICE IN PERMANENT WAY
4) STRAP #4 GROUNDS TO WALL
5) EXPOSE 2ND GROUND ROD (SHOULD BE 6' APART)
6) USE A STAKON LUG ON GREEN STRANDED WIRE IN 4/SQ BOX
7) NEXT TIME YOU USE BRACES ON ROOF FOR RISER USE APPROVED BRACE KIT NOT HOMEMADE
8) COOK TOP OVEN TO BE WORKING AT NEXT INSPECTION
9) WILL FOLLOW UP IN 5 DAYS