Permit: T07CM00220

Parcel: 12108001B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00220

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP C OF O SUBJECT
TO DETERMINATION OF S. LONG

1. NEED CITY APPROVAL STAMP ON REVISIONS
05/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLAN REVISION TO NOTE FOR ADDED 208V ADDED CIRCUIT AND RECEPTACLE DELETIONS.
2. FINISH WORKING CLEARANCES
05/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6
2. KITCHEN CONVENIENCE RECEPTACLES TO BE GFCI PROTECTED - 210.8
3. GROUND POWER POLE JUNCTION BOXES
4. JUNCTION BOXES FOR WALK IN TO BE SEALED PER 300.7 AND GROUNDED 250.148
5. MAINTAIN WORKING CLEARANCE WATER HEATER DISCONNECT.
6. ALL ALUMINUM CONDUCTORS TO USE ANTI-OXIDE COMPOUND.
7. ADJUST PANEL COVER TO 1/4" OR LESS TO SURFACE
8. RECEPTACLE LAYOUT NOT AS PER PLANS - REVISE PLANS OR INSTALL AS PER PLANS.
9. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN SERVICE FOR INSPECTION
10. SUPPORT SEAL TIGHT UP OFF OF ROOF
11. MAINTAIN WORKING CLEARANCES
12. TIGHTEN LOOSE FITTINGS
13. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR
05/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*