Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00220
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP C OF O SUBJECT TO DETERMINATION OF S. LONG 1. NEED CITY APPROVAL STAMP ON REVISIONS |
|
05/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLAN REVISION TO NOTE FOR ADDED 208V ADDED CIRCUIT AND RECEPTACLE DELETIONS. 2. FINISH WORKING CLEARANCES |
|
05/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6 2. KITCHEN CONVENIENCE RECEPTACLES TO BE GFCI PROTECTED - 210.8 3. GROUND POWER POLE JUNCTION BOXES 4. JUNCTION BOXES FOR WALK IN TO BE SEALED PER 300.7 AND GROUNDED 250.148 5. MAINTAIN WORKING CLEARANCE WATER HEATER DISCONNECT. 6. ALL ALUMINUM CONDUCTORS TO USE ANTI-OXIDE COMPOUND. 7. ADJUST PANEL COVER TO 1/4" OR LESS TO SURFACE 8. RECEPTACLE LAYOUT NOT AS PER PLANS - REVISE PLANS OR INSTALL AS PER PLANS. 9. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN SERVICE FOR INSPECTION 10. SUPPORT SEAL TIGHT UP OFF OF ROOF 11. MAINTAIN WORKING CLEARANCES 12. TIGHTEN LOOSE FITTINGS 13. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR |
|
05/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |