Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 04/18/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* FS'S INSTALLED AT PEDICURE CHAIRS ARE NOT SHOWN ON PLAN. REDLINE CHANGES FOR INSPECTION PURPOSES. OK TO COVER PUMPED DISCHARGED REQUIRED FOR INDIRECT WASTE INSTALL TEMP PLUGS IN FS |
|
| 04/16/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* DOOR CODE 1894 ROUGH PLUMBING OK TO COVER GRAVITY DRAIN SPAS REQUIRE A DIRECT CONNECTION PER SEC 709 UPC FLOOR SINKS ARE ONLY FOR PUMPED DISCHARGE SEE CITY HAND OUT FS AT P-4 REQUIRES A TRAP PRIMER |