Permit: T07CM00205

Parcel: 117090050


Addresses:

1011 S 4TH AV

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/18/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECALL GATE & HOUSE MUST BE OPEN FOR INSPECTION
1. RISER CONDUIT BENT OVER ON ROOF - REPLACE
2. SUPPORT 1/2" CONDUIT TO WALL - SECURITY LTG. AROUND HOUSE IN NEED OF REPAIR, NOT WIRED TO CODE.
3. COOLER NEEDS W/P BOX WITH RECEPTS FOR METER/PUMP
4. INSTALL SMOKE DETECTORS IN BEDROOM
5. REPAIR LIGHT FIXTURES, RECEPTACLES, INSIDE
6. WIRING IN PORCH (ROMEX) NOT TO CODE.