Permit: T07CM00203

Parcel: 117150030


Addresses:

128 E CONGRESS ST


Inspection Status: Not Applicable

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM00203

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Not Applicable

Date Description Inspector Results Comments
06/26/2007 ELECTRIC - INTERMEDIATE Not Applicable IVRS - Inspection :*
06/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO CLEAR ECO 100 AMP SERVICE
05/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO COMPLIANCE WITH NOTE #1, #8 & #7
2) PULL CHAIN FIXTURE IN BACK CLOSET NOT WIRED PER CODE
3) BOX MISSING COVERS, EXPOSED SPLICES AT FRONT 2ND FLOOR
4) FIXTURES MISSING COVERS
04/10/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES FOR T07CM00204

1. INSTALL PERMANENT ADDRESS LABEL ON SERVICE.
2. INSTALL COVER PLATE ON J-BOX ABOVE EXISTING OPENING BETWEEN STORES.
3. MISSING PANEL COVER SCREWS
4. 2ND FLOOR FLUORESCENT FIXTURES NOT WIRED PER CODE
EXPOSED WIRING/SPLICES
5. EM. LIGHT 2ND FLOOR NOT WORKING.
6. SUPPORT MC CABLE AT EM. LIGHTS, WITHIN 12" PER CODE
7. EXPOSED WIRING, POWER STRIP NOT WIRED PER CODE, AT REPAIR CORNER 1ST FLOOR.
8. FLUORESCENT LIGHTS AT FRONT WINDOW NOT WIRED PER CODE.
9. PLUG UNUSED OPENINGS IN J-BOXES, FIXTURES, ETC.