Permit: T07CM00198

Parcel: 12701004C

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Permit Number - T07CM00198

Inspection Description - PLUMBING - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/17/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
RMS 110, 111 AND 112 COMPLETE
ADDITION OF BREAKROOM SINKS COMPLETE
LETTER FROM OWNER ACCEPTED FOR FIXTURE CHANGES.
OK FOR TCO IN NEW TOILET RMS 110-112 & BREAKROOMS.
RECALL FOR INSPECTION AT TR RMS 150 & 151
AFTER INSTALLING FIXTURES.
REDLINE PLANS TO SHOW WORK - AS REQUESTED ON 3/22/07
05/17/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
FIXTURE REPLACEMENT IN RMS 150 & 151 UNDER NEW
PERMIT #T07PL00843
05/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE WORK BEFORE CALLING FOR FINAL
05/10/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE APPROVED PLAN
2. REDLINE CHANGES
3. SUPPORT EXP. TANK
4. SHOWER HEAD CONNECTION LEAKING
5. TEMPERING VALVES REQUIRED AT ALL NEW LAVITORYS
6. FIXTURES REQUIRED TO MEET PLAN SPECS
7. NEW SINK P-5 MISSING CLEANOUT AND COCKHOLE COVER
8. YOU HAVE OPEN DRAIN PIPING IN UNFINISHED
TOILET RM - CAP!
9. WORK WAS DONE IN RM 150
UNCOVER AND REVISE PLAN TO SHOW