Permit: T07CM00198

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00198

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PREVIOUS ITEMS
1. RECALL WHEN PLANS ON SITE
05/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING -- 314.20
2. POWER POLES - SUPPORT POLE, INSTALL MISSING HARDWARE, GROUND JUNCTION BOXES, LOOSE FITTINGS.
3. PANEL SCHEDULES TO BE AS PER 404.8 - NO ABBREVIATION AND CORRECT
4. FINISH REVISION OF PLANS WITH STRAP