Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00198
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PREVIOUS ITEMS 1. RECALL WHEN PLANS ON SITE |
|
05/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING -- 314.20 2. POWER POLES - SUPPORT POLE, INSTALL MISSING HARDWARE, GROUND JUNCTION BOXES, LOOSE FITTINGS. 3. PANEL SCHEDULES TO BE AS PER 404.8 - NO ABBREVIATION AND CORRECT 4. FINISH REVISION OF PLANS WITH STRAP |