Permit: T07CM00198

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00198

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/01/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FINISH VDV CABELING
2. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8

OK TO TILE REMAINING ROOMS EXCEPT AS NOTED
04/23/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK RMS. 104, 105, 106, 107, 108, 109, 113, 114, 115,
147, 148, 165

2. NO EXITS OR EM FIXTURES INSTALLED. LEAVE CEILING TILES OPEN IN THESE AREAS FOR INSPECTION.
04/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FILL UNUSED OPENINGS IN BOXES - FITTINGS NOT A SEAL
2. VDV CABLING TO BE PLENUM RATED "T" STAT
3. IF USING SCREWS ON LIGHTS 2 ON CENTER OR 4 ON CORNERS.
4. FINISH HOMERUN BOXES MAKE UP

OK ROOMS 116-138
140-144
OK TO TILE EXCEPT AS NOTED