Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00198
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/01/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABELING 2. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 OK TO TILE REMAINING ROOMS EXCEPT AS NOTED |
|
04/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK RMS. 104, 105, 106, 107, 108, 109, 113, 114, 115, 147, 148, 165 2. NO EXITS OR EM FIXTURES INSTALLED. LEAVE CEILING TILES OPEN IN THESE AREAS FOR INSPECTION. |
|
04/03/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FILL UNUSED OPENINGS IN BOXES - FITTINGS NOT A SEAL 2. VDV CABLING TO BE PLENUM RATED "T" STAT 3. IF USING SCREWS ON LIGHTS 2 ON CENTER OR 4 ON CORNERS. 4. FINISH HOMERUN BOXES MAKE UP OK ROOMS 116-138 140-144 OK TO TILE EXCEPT AS NOTED |