Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM00193

Parcel: 11712001A


Addresses:

110 E PENNINGTON ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00193

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO PLANS ON JOB SITE
2. INSTALL BUBBLE COVER ON GFI RECEPT
3. DISCONNECTS ARE NOT PROPERLY RATED FOR 480V ONLY RATED FOR 240V INSTALL PROPER DISCONNECTS
4. RECALL WHEN READY
09/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GFI SERVICE RECEP WIRED TO 277U
2. BONDING SCREWS CANNOT BE SHEETMETAL MUST BE SUPPLIED MACHINE GREEN SCREWS
3. DISCONNECTS CANNOT BE USED AS J-BOXES
4. PLEASE CORRECT & RECALL
08/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SERVICE RECEPTACLE WITHIN 25' OFF CONDENSING UNITS - NEC 210.63
2. INSTALL BONDING SCREW AT ALL DISCONNECTS
3. CANNOT USE DISCONNECT ENCLOSURES AS JUNCTION BOXES. PLAN SHOWS SEPARATE JUNCTION BOXES AT EACH DISCONNECT AND NEC DOES NOT ALLOW THIS. NEC 312.8
4. CONNECT EQUIPMENT GROUNDING CONDUCTOR
TO 12" X 12" JUNCTION BOX -- NEC 250.148