Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00193
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO PLANS ON JOB SITE 2. INSTALL BUBBLE COVER ON GFI RECEPT 3. DISCONNECTS ARE NOT PROPERLY RATED FOR 480V ONLY RATED FOR 240V INSTALL PROPER DISCONNECTS 4. RECALL WHEN READY |
|
| 09/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GFI SERVICE RECEP WIRED TO 277U 2. BONDING SCREWS CANNOT BE SHEETMETAL MUST BE SUPPLIED MACHINE GREEN SCREWS 3. DISCONNECTS CANNOT BE USED AS J-BOXES 4. PLEASE CORRECT & RECALL |
|
| 08/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SERVICE RECEPTACLE WITHIN 25' OFF CONDENSING UNITS - NEC 210.63 2. INSTALL BONDING SCREW AT ALL DISCONNECTS 3. CANNOT USE DISCONNECT ENCLOSURES AS JUNCTION BOXES. PLAN SHOWS SEPARATE JUNCTION BOXES AT EACH DISCONNECT AND NEC DOES NOT ALLOW THIS. NEC 312.8 4. CONNECT EQUIPMENT GROUNDING CONDUCTOR TO 12" X 12" JUNCTION BOX -- NEC 250.148 |