Permit: T07CM00192

Parcel: 13110034A


Addresses:

5500 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM00192

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED CLEAN BACTERIA REPORT & IN HOUSE BACKFLOW CERTIFICATIONS
02/26/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE CORRECT WATER SUPPLY TO CHEMICAL ADDITIONS AT MOP SINKS (JANITOR FAUCET VACUUM BREAKERS WILL FAIL UNDER CONSTANT PRESSURE AND ARE NOT CORRECT SUPPLY FOR THESE DEVICES)
02/22/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ITEMS LISTED FROM 2/5/08 INSPECTION
02/05/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE 1" AIR GAP FOR ALL INDIRECT DRAIN TERMINATIONS
2. PROVIDE COMPLETED INSTALL OF K.O SYSTEM WITH PIPING TEST
3. PROVIDE PROOF OF 1" AIR GAP OR CORRECT BACKFLOW PROTECTION FOR WATER TO BAKERY OVEN
4. PROVIDE GRATES FOR FLOOR SINKS & DOMES, PROVIDE FUNNELS FOR FLOOR DRAINS WITH INDIRECT DRAINS TERMINATED INTO THEM
5. COMPLETE INSTALL OF SANITIZE SYSTEMS AT BAKERY DELI FOR BACKFLOW PROTECTION
6. FLOOR CLEANOUTS TO BE FLUSH WITH FLOOR FOR NO TRIPPING HAZARD
7. COMPLETE INSULATION ON ALL HOT & COLD PIPING REQUIRED
8. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR DRAINS
AT 3-COMP SINK
9. COMPLETE CORRECT PLUMBING INSTALL AT MG-11 LOCATION
10. COMPLETE INSTALL OF FOUNTAIN BEVERAGE DISPENSERS WITH CORRECT BACKFLOW PROTECTION AND CERTIFICATIONS FOR ALL IN HOUSE DEVICES & ICE MACHINE
01/24/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ALL PLUMBING RELATED INSTALLATIONS.
A CLEAN BACTERIA REPORT FOR POTABLE WATER SYSTEM IS REQUIRED. LIST NOT COMPLETE.