Permit: T07CM00192

Parcel: 13110034A


Addresses:

5500 E 22ND ST

Inspection Status: Approved

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
01/29/2008 SITE - SEWER Approved IVRS - Inspection :*
CLEAN BACTERIA REPORT ON SITE
01/28/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
(2) PRIVATE MANHOLES TO BE CLEAN & PIPING TO BE FREE OF DEBRIS, WITH ACCESS TO TRACER WIRE
11/06/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
RECEIVED A COPY OF VERIFICATION OF GRADE
11/01/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
VACUUM TEST MANHOLE #2 OK
VACUUM TEST MANHOLE #3 OK
10/29/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM PUBLIC MANHOLE #1 TO MANHOLE #2 AIR TEST OK
6" HCS LATERAL FROM MANHOLE #2 TO BLD AIR TEST OK
FROM MANHOLE #2 TO #3 AIR TEST OK
6" HCS LATERAL FROM MANHOLE #3 TO BLD AIR TEST OK
MANDREL FROM MANHOLE #1 TO #2 TO #3 OK
09/21/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
STACK OF MANHOLE #2 & #3 & BASES OK
09/20/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1) 6" FROM MANHOLE #3 TO 5' FROM BLDG BEDDING, LAYING TRACER. WILL AIR TEST PIPING AND VACUUM TEST MANHOLES AT LATER DATE WITH VERIFICATION OF GRADE AT LATER DATE
09/19/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1) 6" SDR 35 FROM MANHOLE #2 TO SOUTH WEST END OF BLDG, BEDDING CASING TRACER OK. SHALL AIR TEST PIPING, VACUUM TEST MANHOLES AND PROVIDE VERIFICATION OF GRADE AT LATER DATE
09/18/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR 35 INSTALLED W/TRACER WIRE BETWEEN MH #1 AND MH #2 VERIFICATION OF GRADE REQUIRED AND TESTING REQUIRED
09/14/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1. 6" SDR 35 INSTALLED BETWEEN MH#2 & MH#3 INSTALLED W/TRACER OK TO COVER SUBJECT TO VERIFICATION OF GRADE AND TEST AT A LATER DATE.
2. CALL FOR NEXT SECTION U.G. INSPECTION
09/13/2007 SITE - SEWER Not ready for Inspection 1. PRIVATE SEWER INSTALLED AND COVERED WITHOUT INSPECTION - NO TRACER WIRE INSTALLED
2. REVIEWED INSTALLATION STANDARD WITH CONTRACTOR