Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T07CM00192
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2008 | SITE - SEWER | Approved | IVRS - Inspection :* CLEAN BACTERIA REPORT ON SITE |
|
01/28/2008 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* (2) PRIVATE MANHOLES TO BE CLEAN & PIPING TO BE FREE OF DEBRIS, WITH ACCESS TO TRACER WIRE |
|
11/06/2007 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* RECEIVED A COPY OF VERIFICATION OF GRADE |
|
11/01/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* VACUUM TEST MANHOLE #2 OK VACUUM TEST MANHOLE #3 OK |
|
10/29/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM PUBLIC MANHOLE #1 TO MANHOLE #2 AIR TEST OK 6" HCS LATERAL FROM MANHOLE #2 TO BLD AIR TEST OK FROM MANHOLE #2 TO #3 AIR TEST OK 6" HCS LATERAL FROM MANHOLE #3 TO BLD AIR TEST OK MANDREL FROM MANHOLE #1 TO #2 TO #3 OK |
|
09/21/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* STACK OF MANHOLE #2 & #3 & BASES OK |
|
09/20/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1) 6" FROM MANHOLE #3 TO 5' FROM BLDG BEDDING, LAYING TRACER. WILL AIR TEST PIPING AND VACUUM TEST MANHOLES AT LATER DATE WITH VERIFICATION OF GRADE AT LATER DATE |
|
09/19/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1) 6" SDR 35 FROM MANHOLE #2 TO SOUTH WEST END OF BLDG, BEDDING CASING TRACER OK. SHALL AIR TEST PIPING, VACUUM TEST MANHOLES AND PROVIDE VERIFICATION OF GRADE AT LATER DATE |
|
09/18/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR 35 INSTALLED W/TRACER WIRE BETWEEN MH #1 AND MH #2 VERIFICATION OF GRADE REQUIRED AND TESTING REQUIRED |
|
09/14/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. 6" SDR 35 INSTALLED BETWEEN MH#2 & MH#3 INSTALLED W/TRACER OK TO COVER SUBJECT TO VERIFICATION OF GRADE AND TEST AT A LATER DATE. 2. CALL FOR NEXT SECTION U.G. INSPECTION |
|
09/13/2007 | SITE - SEWER | Not ready for Inspection | 1. PRIVATE SEWER INSTALLED AND COVERED WITHOUT INSPECTION - NO TRACER WIRE INSTALLED 2. REVIEWED INSTALLATION STANDARD WITH CONTRACTOR |