Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM00192
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/09/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ALL DWV TESTED THRU ROOF OK |
|
01/08/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* MEAT COOLER WATER & DWV OK THRU ROOF TO OVERHEAD IN WALL BREAKROOM OK DWV & WATER 1. PROVIDE APPROVED RECEPTOR FOR INDIRECT DRAINAGE 2. PROVIDE TESTING & REPAIR AT PHARMACY & ALL FLOOR AREA VENTS AND DECK AREA |
|
01/03/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WATER TEST FOR (2) 3" VENT THRU ROOF FOR CWV SYSTEM OK - WATER TEST FOR (3) 2" VENTS THRU ROOF FOR EAST WALL OK - EXPOSE ALL IN WALL PIPING FOR INSPECTION THAT HAS NOT BEEN INSPECTED. |
|
12/28/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV PRODUCE & DELI THRU ROOF WATER TEST OK WATER PIPING PRODUCE & DELI OK PROVIDE CORRECT DRAIN FOR 3-COMP SINK IN DELI |
|
12/20/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NORTHEAST RESTROOM AREA DWV & WATER THRU ROOF OK |
|
12/19/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* MENS & WOMENS LAV WALL ONLY TEST THRU ROOF OK OK TO INSULATE WATER PIPING |
|
12/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
12/13/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |