Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00192
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL CASH OFFICE & CUSTOMER SERVICE 2. OK FINAL @ DELI 3. OK FINAL PRODUCE PREP & DAIRY CASES 4. ONLY 2 EM FIXTURES NOT WORKING 5. STILL NEED TO CHECK PREVIOUS INSPECTION ITEMS |
|
01/28/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/24/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. OK FINAL PHARMACY DOCK AREA 1. INSTALL BONDING BUSHING AROUND CONCENTRICS WHEN 277V TO GROUND 2. HAVE CUT STRANDS ON WIRES TO BOILER 3. NEED PROPER COLORED TAPE ON CONDUCTORS 4. MARK DISCONNECTS FOR EQUIPMENT SERVED 5. ONE GROUND PER TERMINAL 6. OK GAS BOND |
|
01/23/2008 | ELECTRIC - FINAL | Partial Approval | 1. OK FINAL @ PHARMACY EXCEPT UPS RECEPTACLES 2. OK WIRING TO XFMR 3. NEED TO PERFORM GFI TEST OF MAIN SERVICE DISCONNECT 4. OK POWER TO RECEPTACLES @ COLUMNS SALES FLOOR 5. OK POWER TO RECEPTACLES BREAKROOM, OFFICE AND COMPUTER ROOM. |
|
01/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. OK DROP CEILINGS 2. OK FINAL RESTROOMS 3. RECEIVED LETTER OF TORQUE |