Permit: T07CM00186

Parcel: 11516025B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/27/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
12/26/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE NOTES FORM 12/20/07-VENT TO BE CONNECTED DOWNSTREAM OF FIXTURE TRAP
12/24/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) DOOR LOCKED
12/20/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. EACH FIXTURE TRAP REQUIRES A CORRECTING VENT DOWNSTREAM AS SHOWN ON DETAIL #5 P2.1 WASTE ISOMETRIC
2. AT STORAGE AND CHEM STORAGE, ARCHITECT ALLOWS 2 SINKS DUMPING INTO ONE SUMP. HOWEVER, THE MINIMUM WASTE SIZE FOR A SINK IS 2" AND EACH FIXTURE TRAP NEEDS TO BE VENTED.
3. CHECK ALL OTHER SINK LOCATIONS FOR VENTS AND BACKPITCH.
12/18/2007 PLUMBING - FINAL Not ready for Inspection 1. 3/4" VALVE INSTALLED ON A ONE INCH LINE (AT RPPBP) NOT PER CODE
2. SK-3'S AT STORAGE 116 AND CHEM STORAGE 115 NOT INSTALLED PER PLAN. NO REDLINES SHOWING CHANGE,
1001.2 SINKS SET ADJACENT TO, OR SIDE BY SIDE, IN THE SAME ROOM MAY SERVE A SINGLE TRAP.
3. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
12/12/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EACH AND EVERY ITEM ON THE PLAN NEEDS TO BE ADDRESSED. EITHER INSTALL IT PER PLAN OR REVISE THE PLAN. CONTRACTOR SHALL PAY REINSPECTION FEE.
12/06/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEE PLUMBING INSPECTION NOTE #3 FROM 7/12/07 STILL NO REDLINES EACH AND EVERY ITEM ON THE APPROVED PLAN TO BE ADDRESSED, OR PROVIDE A REVISED PLAN
2. SEE PLUMBING PLAN NOTES #19 & #31 PO.1 INSULATION TO BE CONTINUOUS
3. SEE CORRECTION NUMBER 4 FROM 11/15/07
4. YOU MAY WANT TO REVIEW 710.4 & 710.9 2006 UPC
11/15/2007 PLUMBING - FINAL Denied - WH PIPING NOT SIZED PER DETAIL
- ALSO, INSULATE PIPING
- CONDENSATE CONNECTION NOT PER DETAIL
- SUMP DISCHARGE MISSING UNION & CHECK VALVE RECOMMENDED
- IN INSTALLATION MANUAL, ALSO, TEF TAPE SPECIFIED FOR CONNECTION
- LAV CARRIER NOT INSTALLED PER SPEC
- ABV CEILING NOT YET APPROVED