Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK WALLS ROUGH - RECEIVED LETTER FOR APPROVAL OF MC AND CONDUIT SIZES. OK TO USE MC & 1/2" CONDUIT |
|
| 09/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - MC CABLE MUST BE 1 1/4" MIN AWAY FROM FACE OF STUD TO PROTECT FROM SCREWS - PROVIDE LETTER FROM ARCH. FOR APPROVAL OF MC USE AND CONDUIT UNDER 3/4" TRADE SIZE - USE BACK SUPPORTS FOR BOXES IN METAL STUDS |