Permit: T07CM00186

Parcel: 11516025B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/12/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK WALLS ROUGH
- RECEIVED LETTER FOR APPROVAL OF MC AND CONDUIT SIZES. OK TO USE MC & 1/2" CONDUIT
09/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- MC CABLE MUST BE 1 1/4" MIN AWAY FROM FACE OF STUD TO PROTECT FROM SCREWS
- PROVIDE LETTER FROM ARCH. FOR APPROVAL OF MC USE AND CONDUIT UNDER 3/4" TRADE SIZE
- USE BACK SUPPORTS FOR BOXES IN METAL STUDS