Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/27/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/23/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PLANS REQUIRE MIN. 2" DUCT WRAP ON THE OUTSIDE OF ALL DUCTING. IN ANY CASE, ALL DUCT INSULATION IN UNCONDITIONED SPACES MUST BE MIN. R-5 1" DUCT LINER IS R4.2 PROVIDE A LETTER FROM THE ENGINEER IF YOU ARE GOING TO USE LINED DUCT. |