Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07CM00178
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
06/04/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DOUBLE CHECK REQUIRED AT NON-CARBONATED BEVERAGES. TEST REQUIRED. 2. PROPERLY INSTALL PVC DRAIN FROM SODA I.E SUPPORT, ROUTING AND PRIMER 3. CORRECT SLOPE AT 3-COMP SINK 4. INDIRECT DRAINS REQUIRE CLEANOUTS AND WYE PATTERN FITTINGS. 5. SEPARATE CONDENSATE FROM ICE BIN DRAIN, SUPPORT PIPING. 6. CORRECT SLOPE AT T & P 7. PROVIDE BACKFLOW PROTECTION FOR OR ELIMINATE SECOND ICE MACHINE SUPPLY 8. PAINT EXPOSED PLASTIC VENT TERMINATIONS. |
|
06/01/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* HOOK UP ALL EQUIPMENT MAKE ALL CONNECTIONS INSTALL ALL PIPING, BEFORE CALLING FINAL |
|
05/31/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PAT @ 409-1156 |
|
05/30/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CLOSET FLANGES ARE OK |
|
05/29/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |