Permit: T07CM00178

Parcel: 11008305F


Addresses:

2485 N SWAN RD #161

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/30/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/29/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS
RECALL FOR CLOSET FLANGE INSP.
04/27/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WILDAN STAMP VISIBLE ON REDUCED SET
2. CORRECT SLOPE AND EXTEND CLEANOUTS AT
HS & 3 COMP SINK
3. HAMMER ARRESTORS REQUIRED FOR FLUSH O METERS
4. UNIONS ON TRAP PRIMERS
5. SUPPORT HORIZONTAL VENT ABV T.R
6. OK TO INSULATE ABV CEILING. OK TO COVER WALLS EXCEPT AT 3-COMP SINK.
04/23/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
SEE NOTES FROM #1 3/26/07
AND FINAL NOTE FROM 4/2/07 AND COMPLY