Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CONDUIT ABOVE PANEL. ONE WRAP PER CONDUIT NOT GROUP SUPPORTS. 2. PROTECT MC CABLE WHERE TIED TO SIDES 3. FINISH #4 & #5 PREVIOUS INSPECTION |
|
| 04/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT M/C CABLES WITHIN 12" OF BOXES AND ON VERTICALS 2. TIGHTEN LOOSE CONDUIT FITTINGS 3. FILL UNUSED OPENINGS IN BOXES 4. SUPPORT CONDUIT RUNS ABOVE PANEL AS PER CODE 5. PROTECT M/C CABLE TOP PLATE BATHROOM OK TO ONE SIDE. |