Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/28/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK CEILING AFTER CORRECTIONS TO CEILING 1. SUPPORT MC CABLE TO MOVED LIGHTS 2. REMOVE ABANDONED CABLING 725.3 3. LABEL DISCONNECT 4. ATTACH DISCONNECT TO STRUCTURE 5. TIGHTEN LOOSE FITTING 6. TIGHTEN CONDUCTOR TERMINATIONS 7. BOND DISCONNECT 8. USE APPROVED HARDWARE FOR SUPPORTS AND CORRECT SIZE STRAPS *VERIFY LIGHTING ADDED IN WALL - POOL ROOM 9. BOND JUNCTION BOX ENCLOSURE |