Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM00137
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
06/07/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL SCREWS FROM DRYER VENTS 2. PROVIDE SCREWS IN EXHAUST FAN DUCT CONNECTION 3. PROVIDE P.G ON ALL SIDES OF RETURN CEILING CAN & BACKING. 4. PROVIDE PLATE STRAPS AT KITCHEN EXHAUST 5. DO A BETTER JOB SECURING DRYER BOXES. 6. DO NOT INSULATE T-WYES W/TAPE. MUST USE INSULATION 7. RELOCATE BATHROOM EXHAUST FANS FROM ABOVE THE SHOWER. |