Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM00135
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/27/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLOSET FLANGES NOT APPROVED 2) CONTRACTOR TO PAY REINSPECTION FEE |
|
09/21/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE UPC SECS 316 AND INSTALLATION STANDARDS FOR ABS CLOSET FLANGES |
|
09/18/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/21/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ALL AREAS NEED TO SEE FIRST FLOOR FLANGES |
|
05/18/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ABS IS TO BE SUPPORTED AT EACH FLOOR AND MID-STORY SUPPORT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES -- THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. ALL CLOSET FLANGES ARE TO BE SECURED TO THE FLOOR WITH CORROSION RESISTANT SCREWS. |