Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T07CM00135
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
10/29/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THERE IS NO GROUNDING ELECTRODE TO THIS SERVICE 2. BONDING JUMPER TO RISER TO BE MIN. #2 COPPER 3. NEED CORRECT UNIT NUMBERS, PROPERLY ATTACHED 4. INSTALL MISSING SCREWS, CLEAN DEBRIS OUT OF SERVICE |
|
09/21/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
09/19/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
08/17/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* REVIEW ITEMS FOR #100 |