Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T07CM00134
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
10/29/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The service is not per code.| 210* SEE T07CM00135 |
|
09/24/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/21/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
08/17/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICES TO BE PERMANENTLY ADDRESSED/ALSO SPACE #'S 2. CLAMP TO BE TIED AT BOTTOM OF SERVICE 3. 2 1/2" RIGID CONDUIT ENTRY DAMAGED AT BOTTOM OF SERVICE 4. BOND JUMPER REQUIRED ON 2 1/2" BOND BUSHING TO ENCLOSURE 5. UFER TO BE TIED TO CORRECT LOCATION 6. ARC-FAULT BREAKERS IN PANEL? |