Permit: T07CM00122

Parcel: 134221190


Addresses:

6802 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/15/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CLOSET FLANGES OK
REVISED APPROVED PLAN ON SITE
02/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) APPROVED PLAN SHOWS 4 STOOLS, 4 LAVS AS EXISTING-CONTRACTOR HAS REMOVED 2 STOOLS AND 2 LAVS ON SITE PLUMBING FIXTURES ADDITIONAL INSTALLED WITHOUT INSPECTION OR FIXTURE CONNECTION ? ARE 1 URINAL, 1 JANITOR SINK, 1 LAV, 1 STOOL, 1 SHOWER AND 1 FLOOR DRAIN
INSTALLATION OF URINAL AND FLOOR DRIN ARE INSPECTED THIS INSPECTION OK
REVISED CITY OF TUCSON APPROVED PLANS TO SHOW ALL FIXTURES WITH PROOF OF CONNECTION FEES
02/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ADDITION OF CLEANOUT FOR BREAKROOM SINK OK
2) SEE PAST INSPECTION NOTES, PROVIDE PLUMBING PLANS OF ANY ADDITONAL FIXTURES
02/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PERM CAPS FOR EAST RESTROOM FLOOR DRAIN OK
2) WEST RESTROOM CURRENTLY HAS ADDED URINAL, WHICH WOULD REQUIRED FLOOR DRAIN WITH TRAP PRIMER IN REST ROOM-ALL OF WHICH WOULD BE REQUIRED ON REVISED APPROVED PLAN. REVISED APPROVED PLAN REQUIRED FOR EXISTING JANITOR SINK, STOOL, SHOWER, LAV AND BREAK ROOM SINK AND ICE MAKER CONNECTION FOR REFRIDGERATOR. BREAK ROOM SINK HAS INSTA-HOT WATER HEATER TO BE ADDED TO PLAN. 1-BREAK ROOM SINK ADDED WITHOUT INSPECTION REQUIRES CLEANOUT. PUBLIC USE LAVS REQUIRE MEANS TO CONTROL HOT WATER TEMPERATURE MAX OF 120 DEGREES BESIDES WATER HEATER
01/25/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. EAST RESTROOM OK AFTER FLOOR DRAIN IS PERMANENTLY CAPPED AND INSPECTED.
2. WEST RESTROOM SHALL HAVE URINAL REMOVED, FLOOR DRAIN REMOVED & PERM. CAPPED. GALV CAP ON WATER PIPING TO BE REMOVED.
3. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN TO DAYLIGHT.
4. JANITOR SINK TO BE ADDED TO REVISED APPROVED PLAN OR PERM CAPPED & REMOVED.
SAME WITH BREAKROOM SINK & ICE MAKER
A MEANS FOR WATER HAMMER ARRESTOR SHALL BE USED FOR ALL QUICK ACTING VALVES.
5. ADDITIONAL RESTROOM WITH SHOWER SHALL BE ADDED TO REVISED APPROVED PLAN IF DESIRED.
6. ANY PLUMBING FIXTURES THAT ARE NOT ON YOUR CURRENT APPROVED PLAN WILL REQUIRE EXPOSURE OF PIPING FOR INSPECTION.