Permit: T07CM00120

Parcel: 107060560

Inspection Status: Approved

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
07/31/2007 SITE - SEWER Approved IVRS - Inspection :*
07/16/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*

POST YOUR ADDRESS
NOT INSTALLED PER PLAN NO REDLINES ON SITE.

ABS REQUIRES 12" OF COVER AT ALL POINTS
ABS TO BE LAID ON A FIRM BED NOT BRIDGING PERMITTED
ABS TO HAVE A UNIFORM SLOPE OF 1/4" PER FOOT