Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/14/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED 2 GROUND RODS FOR PANEL "M" NEC 250.32 B1 2) IDENTIFY PANEL "M" BREAKERS NEC 408.4 3) ALL GROUND RODS TO BE DRIVEN FLUSH, NOT BENT OVER AND A MINIMUM 6' APART 250.52 |