Permit: T07CM00094

Parcel: 134180100


Addresses:

7342 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/22/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK WALLS
03/19/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SCREWS NOT ALLOWED IN FRONT PORTION OF
BOX 314.23
2. USE NM CONNECTOR AS PER LISTING FOR NUMBER OF CABLES.
3. TIGHTEN LOOSE CONNECTORS
4. PLANS NOT REFLECTIVE OF WORK - SHOW ALL RECEPTACLES EXISTING & NEW - ALSO, WHERE IS PANEL SCHEDULE AND LOADS.
5. PLEASE HAVE ARCHITECT VERIFY USAGE OF NM CABLE FOR NEW WIRING.
6. MOVE JUNCTION BOXES OUT PAST DRYWALL EDGE SO AS TO NOT BE COVERED.