Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK WALLS |
|
| 03/19/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SCREWS NOT ALLOWED IN FRONT PORTION OF BOX 314.23 2. USE NM CONNECTOR AS PER LISTING FOR NUMBER OF CABLES. 3. TIGHTEN LOOSE CONNECTORS 4. PLANS NOT REFLECTIVE OF WORK - SHOW ALL RECEPTACLES EXISTING & NEW - ALSO, WHERE IS PANEL SCHEDULE AND LOADS. 5. PLEASE HAVE ARCHITECT VERIFY USAGE OF NM CABLE FOR NEW WIRING. 6. MOVE JUNCTION BOXES OUT PAST DRYWALL EDGE SO AS TO NOT BE COVERED. |