Permit: T07CM00093

Parcel: 13322471B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/23/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
(8) IN HOUSE BACKFLOW CERTIFICATIONS FOR FOOT SPAS
(1) BACTERIA REPORT FOR POTABLE WATER
05/17/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SEE NOTE ABOVE (5/14/07 INSPECTION) ABOUT FOOT SPAS
NO PROBLEM FOR TEMP C OF O FOR STOCKING ONLY.
05/14/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE CHECK VALVES FOR PUMPED DISCHARGE AT FOOT SPA CHAIRS AND PROVIDE CORRECT BACKFLOW PROTECTION PER PLAN M4.0 NOTE #2 A&B, Bii

1. SHALL PROVIDE CLEAN BACTERIA REPORT FOR POTABLE WATER.
2. PROVIDE ACCESS TO ALL CLEANOUTS. WATERPROOF ALL FIXTURES.
3. ALL FIXTURES TO BE FUNCTIONAL
4. PROVIDE APPROVED GAS VALVES & FLEXES FOR DRYERS
5. COMPLETE GAS PIPING WITH VALVE TO WATER HEATER & PROVIDE COMBUSTION AIR.
6. TERMINATE T&P DRAIN, SUPPORT EXPANSION TANK, COMPLETE HOT & RETURN INSULATION.