Permit: T07CM00093

Parcel: 13322471B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. METAL NOT APPROVED EXTENDER RINGS 314.20, 110.3
2. PANEL DIRECTORIES TO BE AS PER 404.8 -- NO ABBREVIATIONS
3. BOX OVERFILL AT INSTA HOT/WH SWITCH
4. SECURE CABLES & CORDS TO HW TANK & OTHER BOXES AND CABINETS
5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NON-COMBUSTIBLES 314.20
6. EM LIGHTING & EXIT LIGHTING TO BE AS PER 700.12
7. USE APPROVED HARDWARE WITH BOXES - NOT SHEETMETAL OR DRYWALL THREADS.
8. INSTALL FLOOR BOX DEVICE COVER AS PER MANUFACTURES INSTRUCTIONS
9. FINISH #1 OF INSPECTION 5/11/07