Permit: T07CM00093

Parcel: 13322471B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/15/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BOXES IN COMBUSTIBLES TO BE FLUSH -- 314.20
2. FINISH VDV CABLING - EXPLAINED TO CONTRACTOR THE CODES.

OK STATION (CENTER) RECEPTACLES.
05/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT VDV CABELING TO BE AS PER 425.6, 800.6 AND 300.11
2) SCREWS NOT ALLOWED IN FRONT PORTION OF BOXES 312.23
3) FINISH VDV AT FRONT COUNTER
04/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FROM WALLS
OK PANEL WALLS
04/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT M/C CABLE UPON EXITING WALLS
2. FINISH PANEL WALLS

OK WALLS EXCEPT AS NOTED
03/29/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS 106, 109-114
03/28/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROTECT M/C CABLE IN CHANNEL
2. USE APPROVED M/C FITTINGS
3. SCREW NOT ALLOWED IN FRONT PORTION OF BOX 314.23
4. BOX OVERFILLED

OK FRONT WALL & UP HIGH
03/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK THE REST OF DEMISING WALL
03/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE

OK DEMISING WALL SUBJECT TO LETTER