Permit: T07CM00081

Parcel: 10311037H


Addresses:

3051 W NEOSHA ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/07/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/24/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #4 ALUM CONDUCTOR AT 75 PERCENT IS ONLY ALLOWED 65 AMPS PRESENTLY IN A 100 AMP CIRCUIT
2) PLASTIC BUSHING MUST BE INSTALLED PANEL KNOCKOUT FOR MAIN FEED
3) NAIL PROTECTION MUST BE MINIMUM 16 GAUGE
4) MAKE UP CONNECT ALL GROUND WIRES IN ELECTRIC BOXES AND SECURE WITH A MECHANICAL FASTENER
08/23/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO ADD SUB-PANEL TO PERMIT
2. NEED TO PUT PROTECTION PLATES ON WIRES LESS THAN 1 1/4" FROM EDGE OF STUD NAILERS