Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM00072
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
01/23/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE B-VENT AT WATER HEATER PENETRATION THROUGH ROOF ON EXTERIOR WATER HEATER ALL INTERIOR OK |
|
01/03/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #1 - PROVIDE 1" CLEARANCE TO COMBUSTIBLES ON FLUE "B" VENT - PROVIDE DIRT LEG ON GAS TO FURNACE AND ALL OTHER BACK DRAFT DAMPER ON RANGE HOOD. - FASTEN ELBOW TO WATER HEATER RISER #2 - BACK DRAFT DAMPER ON HOOD - DIRT LEGS ON GAS - CLEARANCE TO COMBUSTIBLES - EXTERIOR WATER HEATER FLUE PIPE ABOVE WALL |