Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00072
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR UNIT #2 1. NEED LIGHT FIXTURE OR SWITCHED RECEPTACLE FOR BEDROOMS 2. INSTALL RANGE ANTI-TIP DEVICE 3. USE ONLY SQ D BREAKERS IN SQ D PANEL 4. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED 5. BATHROOM RECEPTACLES TO BE GFI PROTECTED 6. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 7. EXTERIOR RECEPTACLES TO BE GFI PROTECTED 8. NEED COUNTERTOP RECEPTACLE BETWEEN RANGE AND REFER 9. HAVE SEVERAL LOOSE RECEPTACLES 10. SMOKE DETECTOR TO BE MINIMUM 36" AWAY FROM HVAC VENT 11. PROVIDE SERVICE RECEPTACLE FOR HVAC UNIT INSPECTION FOR UNIT #2 ONLY - CHECK SAME #1 - NO PLANS ON SITE? |