Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM00069
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* - FLEX DUCTS NOT INSTALLED PER DETAILS ON PLANS - USE ONLY UL LISTED DUCT TAPE AS PER IMC - PROVIDE OVERFLOW SENSORS AS PER PLAN - PROVIDE BUSHINGS AROUND REFER LINE CONNECTIONS TO FAN COIL - READJUST SUPPORTS ON FC-1 BLOCKING SERVICE PANEL - SECURE SUPPORTS TO STRUCTURE - FINISH INSULATING REFER LINES - T-STATS TO BE ADA HEIGHT 48" MAX - REVISE PLANS SHOWING PROPER LOCATION OF CONDENSORS |