Permit: T07CM00069

Parcel: 12811424B


Addresses:

4910 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T07CM00069

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2008 PLUMBING - ROUGH, SOIL Approved
09/16/2008 PLUMBING - ROUGH, SOIL Approved per PL FINAL
01/23/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VENT FITTING TO BE INSTALLED TO DRAIN BACK TO DIRECTION OF SEWER FLOW
2. NO THREADED ABS FITTING SHALL BE IN AN UNACCESSIBLE LOCATION.
3. VENT TO BE EQUAL TO CROSS-SECTIONAL AREA OF REQUIRED BUILDING SEWER
4. VENT FITTING BELOW FLOOD LEVEL RIM TO BE LONG RADIUS
01/18/2008 PLUMBING - ROUGH, SOIL Partial Approval - FROM SEWER MAIN 4" BACK TO EXISTING BUILDING
- SEWER CONNECTION WATER TEST OK
- SHALL SEE FINAL CONNECTION AND VENT FOR BACKWATER VALVE
01/10/2008 PLUMBING - ROUGH, SOIL Partial Approval INSTALLATION OF BACKWATER VALVE PER PLAN WITH WATER TEST TO 2' PAST IN LINE CLEANOUT OK

NOTE: PLEASE SEE CHAPTER 9 2003 UPC FOR SECTION 904.1
FOR REQUIREMENT FOR VENTING OF SANITARY SYSTEMS WITH BACKWATER VALVES.
11/14/2007 PLUMBING - ROUGH, SOIL Approved
11/07/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" FROM 2' BUILDING EXTERIOR WEST SIDE THRU BUILDING PER PLAN

1. SHALL SEE REDLINE & CONTINUATION OF SEWER THRU BACKWATER VALVE CLEANOUTS TO EXISTING.