Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T07CM00069
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
01/18/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST BOND FOR TEMP PWR TO TEST 2. PVC SEPARATED AT COUPLING UNDER METER 3. SECURE RISER TO BUILDING 4. REMOVE MAIN BONDING JUMPER @ SUB-PANEL 5. EXPLAIN JUMPER FROM GROUND BAR TO METER 6. BONDING JUMPER TO RISER & NIPPLE FROM METER TO PANEL NOT SIZED PROPERLY 7. REMOVE PAINT AND DEBRIS FROM PANELS AND BUS BARS AND BREAKERS |