Permit: T07CM00069

Parcel: 12811424B


Addresses:

4910 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T07CM00069

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
02/11/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/18/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK WALLS
2. OK 2 1/2" PVC FROM TEP PULL BOX TO SES
3. OK 3/4" PVC FOR WALL LIGHT
4. OK 3/4" PVC FOR BALLARD LIGHT FROM BUILDING TO 1ST LIGHT
5. PROVIDE LETTER FROM ENGINEERING APPROVING CHANGE IN PVC SIZE
6. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTORS PER NEC 300.5
11/07/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK FLOOR BOXES IN SLAB & ASSOCIATED PVC CONDUITS