Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07CM00016
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/17/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE ACCESS TO VALVE & TRAP PRIMER IN WOMENS RESTROOM 2. PROVIDE CLEANOUT PLUG IN NEW LAUNDRY STACK 3. COMPLETE NOTES #4, #5 AND #6 RECEIVED BACTERIA REPORT FOR POTABLE WATER AND BACKFLOW CERTIFICATIONS |
|
| 12/11/2008 | PLUMBING - FINAL | Not ready for Inspection | 1. MAKE REPAIR TO TRENCH DRAIN AT 3RD LEVEL PARKING RAMP 2. MAKE REPAIR TO 4TH LEVEL PARKING RAMP AREA DRAIN AT LANDING 3. HAVE SITE SEWER APPROVED (SEPARATE PERMIT) WITH PCDEQ AUTHORIZATION TO DISCHARGE 4. PROVIDE LABELING IN CARWASH FOR RECLAIMED & POTABLE WATER SYSTEMS 5. PROVIDE APPROVED PLANS FOR NEW LAUNDRY AT WEST SIDE WITH CORRECT BUILDING DRAIN AND BUILDING SEWER SHOWN 6. COMPLETE C/O's AT NORTH BUILDING COLUMNS 7. FIXTURES TO BE FUNCTIONAL WITH RESTROOM PARTITIONS 8. EXTERIOR C/O's TO BE TO GRADE LIST MAY NOT BE COMPLETE |
|
| 12/10/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* FIXTURES INSTALLED IN RESTROOM #303, 304, 305, CHLORINIZATION IN PLACE 1. CALL IN ALL INSPECTIONS FOR PLUMBING ON YOUR ACTIVITY CARD |
|
| 06/20/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED BACTERIA REPORT FOR SALES & SERVICE BUILDING FOR POTABLE WATER SYSTEM RECEIVED IN HOUSE BACKFLOW CERTIFICATION FOR ICE MACHINE 1. NEED CORRECT INSTALL OF FLOW CONTROL AT 3-COMP SINK FOR SALES FINAL AND RESTROOM PARTITIONS FOR CLEARANCES |
|
| 06/19/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* (THIS INSPECTION FOR SALES AREA ONLY) 1. COMPLETE INSULATION ON HOT & RETURN PIPING 2. MAKE AIR FIXTURES WATER TIGHT 3. INSTALL RESTROOM PARTITIONS FOR CORRECT ACCESSIBILITY 4. PROVIDE FULL SIZE CONDENSATE CONNECTION AT LAVS 5. PROVIDE SEPARATE MAILER & CONDENSOR DRAINS FOR ICE MACHINE & SECURE WATER SUPPLY PROPERLY 6. COMPLETE INSTALL OF 3-COMP SINK CORRECTLY 7. COMPLETE INSTALL OF ALL FIXTURES INCLUDING SINK GRATES AND DOMES 8. PROVIDE CORRECT BACKFLOW PROTECTION FOR HAND SPRAYER AT 2-COMP SINK IN CAFE AREA 9. ALL PUBLIC USE LAVS REQUIRE TEMPERING 10. PROVIDE BACTERIA REPORT |
|
| 06/16/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* SERVICE AREA OK, RECEIVED CLEAN BACTERIA REPORT FOR POTABLE WATER SYSTEM, (28) IN HOUSE BACKFLOW CERTIFICATIONS. WILL NEED TO SEE CONTINUATION OF GAS PIPING AT SOUTHWEST CORNER TO PRESSURE WASHER. |
|
| 06/13/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/11/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE CLEAN BACTERIA REPORT FOR THIS INSPECTION FOR SERVICE AREA ONLY 2. PROVIDE BACKFLOW CERTIFICATIONS 3. ALL DRAINS TO BE FLUSH WITH FLOOR, WITH COVERS, GRATES, ETC. 4. ALL FIXTURES TO BE INSTALLED AND OPERATIONAL 5. SEAL PIPE PENETRATION INTO BLD. |