Permit: T07CM00016

Parcel: 135084520


Addresses:

7150 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00016

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK MAKE UP IN U.G. JUNCTION BOX EAST SIDE OF DRIVE
2. OK POWER TO GFI RECEPT EAST OF DRIVE @ 22ND ST
3. OK OUTDOOR WALL PACK FIXTURES
02/06/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK U.G FROM PULL BOX TO SIGN LOCATION EAST LOT
2. OK GROUNDING MAKE UP TO DISCONNECTS FOR AIR COMPRESSORS.
01/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK U.G FOR RECEPTS & SIGN WEST LOT
2. OK GFI RECEPTS @ DRIVEWAY ENTRANCE
EAST OF WEST LOT
01/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSPECTION OF LUBE AREA
2. NEED TO INSTALL BONDING BUSHINGS & MARK DISCONNECTS FOR LOAD SERVED
01/23/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FLOOR RECEPTACLES USED CAR SALES
01/21/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK LIGHT RESTROOMS USED CAR SALES
2. WHAT IS TOTAL OUTDOOR LUMENS FOR LIGHTING IF MORE THAN 100,000 LUMENS, REQUIRES SPECIAL INSPECTION
3. OK MAKE UP POLE LIGHTS WEST LOT
12/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FINAL CAR WASH
2. OK RELOCATION OF SPRINKLER PIPE
3. OK EXITS 4TH FLOOR OF PARKING GARAGE
12/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CARWASH
1. BOND RACEWAYS INTO PLASTIC JUNCTION BOXES SEE NOTE ON CONTROL PANELS
2. NEED 1/4" AIR GAP ON METAL RACEWAYS
3. MARK DISCONNECTS FOR LOADS SERVED
4. CHECK ALL CONNECTIONS WATER TIGHT

PARKING GARAGE
1. OK POLE LIGHTS 4TH FLOOR
2. OK LOW VOLTAGE WIRING CEILING USED CAR SALES
3. OK EM LIGHTING SOUTH STAIRWELL
12/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK CEILINGS USED CAR SALES MAKE CORRECTIONS AS DISCUSSED, SPRINKLER PIPE & LOW VOLTAGE CABLE
2. OK PARTIAL FINAL USED CAR SALES, REV. POLARITY GFI,
ARCH FLASH STICKERS. FLOOR RECEPTS
12/10/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
USED CARS:
1. LOW VOLTAGE CABLES TO BE PROPERLY SUPPORTED UP AND OFF CEILING GRID
2. EXIT SIGNS NEED SEISMIC WIRE
3. EM LIGHTS NEED SEISMIC WIRES
4. SPRINKLER PIPING IN EQUIPMENT DEDICATED SPACE NEEDS TO BE MOVED
5. CANNOT USE CEILING TIE WIRES FOR SUPPORT OF LOW VOLTAGE WIRES NEED INDEPENDENT WIRES
6. NO FINAL INSPECTION UNTIL CEILING PASSES
12/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FINAL 3RD FLOOR PARKING GARAGE
2. OK LIGHTS 3RD, 4TH FLOOR RAMPS
3. OK LIGHTING NORTHWEST STAIRWAY
12/02/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK MAKE UP IN PANELS AND XFMRS USED CAR SALES
2. OK POWER TO RECEPTACLES 4TH FLOOR GARAGE
11/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FINAL 2ND FLOOR OF PARKING GARAGE NOT TO INCLUDE RAMPS OR STAIRWAYS
11/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL 1ST FLOOR GARAGE
1ST BAY AREA EAST ONLY
09/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK U.G PARKING GARAGE FROMEAST COLUMN TO CENTER COLUMN HEADING TO ELECTRIC CLOSET
2. OK 50' 2 1/2" PVC UG FOR PANEL FEED 480V
3. OK 4 - 1" PVC FROM ELECTRIC CLOSET NORTH 90'
4. NEED TO INSPECT SIGN @ DELI
5. OK EM LIGHTS @ NEW BUILDING
06/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK ROOF MAIN BUILDING FOR FINAL
2. OK PARTIAL FINAL INTERIOR MAIN BUILDING STILL
HAVE 3 EM LIGHTS NOT WORKING
06/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK EM LIGHTS SERVICE AREA
06/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO OUTDOOR INSPECTION DONE
2. NEED TO MAKE CORRECTIONS ON LIST DONE BY ELECTRICAL CONTRACTOR. RECALL WHEN READY.
3. CHECK WITH BUILDING INSPECTOR FOR OCCUPANCY REQUIREMENTS
4. THIS IS AFTER HOURS INSPECTION. BUILDING INSPECTOR HAS CHECK FOR AFTER HOURS INSPECTION. 4 HOURS OF INSPECTION DONE.
06/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF INSPECTION FRONT HALF
1. PROPERLY FUSE ROOF TOP UNITS
06/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK ROOF AREA ABOVE SERVICE BAYS
2. WILL NEED APPROVED PLANS FOR LIGHTING IN SERVICE AREA. CHECK WITH LEE RAY HANLY FOR EMERGENCY LIGHTING REQUIREMENTS FOR SERVICE AREA.
06/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SERVICE AREA

1. NEED REVISED & APPROVED PLANS FOR LIGHTING CHANGES SERVICE AREA
2. ALL ELECTRICAL EQUIPMENT TO BE ABOVE 18"
3. CHECK EM LIGHTS OUTDOOR WET LOCATION RATED