Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00016
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK MAKE UP IN U.G. JUNCTION BOX EAST SIDE OF DRIVE 2. OK POWER TO GFI RECEPT EAST OF DRIVE @ 22ND ST 3. OK OUTDOOR WALL PACK FIXTURES |
|
| 02/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK U.G FROM PULL BOX TO SIGN LOCATION EAST LOT 2. OK GROUNDING MAKE UP TO DISCONNECTS FOR AIR COMPRESSORS. |
|
| 01/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK U.G FOR RECEPTS & SIGN WEST LOT 2. OK GFI RECEPTS @ DRIVEWAY ENTRANCE EAST OF WEST LOT |
|
| 01/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSPECTION OF LUBE AREA 2. NEED TO INSTALL BONDING BUSHINGS & MARK DISCONNECTS FOR LOAD SERVED |
|
| 01/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FLOOR RECEPTACLES USED CAR SALES |
|
| 01/21/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK LIGHT RESTROOMS USED CAR SALES 2. WHAT IS TOTAL OUTDOOR LUMENS FOR LIGHTING IF MORE THAN 100,000 LUMENS, REQUIRES SPECIAL INSPECTION 3. OK MAKE UP POLE LIGHTS WEST LOT |
|
| 12/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL CAR WASH 2. OK RELOCATION OF SPRINKLER PIPE 3. OK EXITS 4TH FLOOR OF PARKING GARAGE |
|
| 12/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CARWASH 1. BOND RACEWAYS INTO PLASTIC JUNCTION BOXES SEE NOTE ON CONTROL PANELS 2. NEED 1/4" AIR GAP ON METAL RACEWAYS 3. MARK DISCONNECTS FOR LOADS SERVED 4. CHECK ALL CONNECTIONS WATER TIGHT PARKING GARAGE 1. OK POLE LIGHTS 4TH FLOOR 2. OK LOW VOLTAGE WIRING CEILING USED CAR SALES 3. OK EM LIGHTING SOUTH STAIRWELL |
|
| 12/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK CEILINGS USED CAR SALES MAKE CORRECTIONS AS DISCUSSED, SPRINKLER PIPE & LOW VOLTAGE CABLE 2. OK PARTIAL FINAL USED CAR SALES, REV. POLARITY GFI, ARCH FLASH STICKERS. FLOOR RECEPTS |
|
| 12/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* USED CARS: 1. LOW VOLTAGE CABLES TO BE PROPERLY SUPPORTED UP AND OFF CEILING GRID 2. EXIT SIGNS NEED SEISMIC WIRE 3. EM LIGHTS NEED SEISMIC WIRES 4. SPRINKLER PIPING IN EQUIPMENT DEDICATED SPACE NEEDS TO BE MOVED 5. CANNOT USE CEILING TIE WIRES FOR SUPPORT OF LOW VOLTAGE WIRES NEED INDEPENDENT WIRES 6. NO FINAL INSPECTION UNTIL CEILING PASSES |
|
| 12/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL 3RD FLOOR PARKING GARAGE 2. OK LIGHTS 3RD, 4TH FLOOR RAMPS 3. OK LIGHTING NORTHWEST STAIRWAY |
|
| 12/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK MAKE UP IN PANELS AND XFMRS USED CAR SALES 2. OK POWER TO RECEPTACLES 4TH FLOOR GARAGE |
|
| 11/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL 2ND FLOOR OF PARKING GARAGE NOT TO INCLUDE RAMPS OR STAIRWAYS |
|
| 11/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL 1ST FLOOR GARAGE 1ST BAY AREA EAST ONLY |
|
| 09/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK U.G PARKING GARAGE FROMEAST COLUMN TO CENTER COLUMN HEADING TO ELECTRIC CLOSET 2. OK 50' 2 1/2" PVC UG FOR PANEL FEED 480V 3. OK 4 - 1" PVC FROM ELECTRIC CLOSET NORTH 90' 4. NEED TO INSPECT SIGN @ DELI 5. OK EM LIGHTS @ NEW BUILDING |
|
| 06/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK ROOF MAIN BUILDING FOR FINAL 2. OK PARTIAL FINAL INTERIOR MAIN BUILDING STILL HAVE 3 EM LIGHTS NOT WORKING |
|
| 06/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK EM LIGHTS SERVICE AREA |
|
| 06/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NO OUTDOOR INSPECTION DONE 2. NEED TO MAKE CORRECTIONS ON LIST DONE BY ELECTRICAL CONTRACTOR. RECALL WHEN READY. 3. CHECK WITH BUILDING INSPECTOR FOR OCCUPANCY REQUIREMENTS 4. THIS IS AFTER HOURS INSPECTION. BUILDING INSPECTOR HAS CHECK FOR AFTER HOURS INSPECTION. 4 HOURS OF INSPECTION DONE. |
|
| 06/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF INSPECTION FRONT HALF 1. PROPERLY FUSE ROOF TOP UNITS |
|
| 06/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK ROOF AREA ABOVE SERVICE BAYS 2. WILL NEED APPROVED PLANS FOR LIGHTING IN SERVICE AREA. CHECK WITH LEE RAY HANLY FOR EMERGENCY LIGHTING REQUIREMENTS FOR SERVICE AREA. |
|
| 06/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SERVICE AREA 1. NEED REVISED & APPROVED PLANS FOR LIGHTING CHANGES SERVICE AREA 2. ALL ELECTRICAL EQUIPMENT TO BE ABOVE 18" 3. CHECK EM LIGHTS OUTDOOR WET LOCATION RATED |