Permit: T07CM00016

Parcel: 135084520


Addresses:

7150 E 22ND ST

Inspection Status: Approved

Inspection History: FIREWALL/FIREBARRIER/FIRESTOP

Date Description Inspector Results Comments
03/25/2009 FIREWALL/FIREBARRIER/FIRESTOP Approved IVRS - Inspection :*
06/18/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1. CONCRETE APPLICATION FOR FLOOR CUTS OK IN COMPUTER/PHONE ROOM. RECALL WHEN FIRESTOP IS COMPLETE. YOU MUST FIRESTOP CONDUIT OPENINGS.
2. 3HR WALL COMPLETE EXCEPT CAMERA WIRING
SLEEVE IN 2ND FLOOR STORAGE
05/05/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1. HAVE ALL FIRESTOP DONE NOT JUST ONE TRADE
2. 3-HR WALL TO AREA B OK
03/26/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
PLUMBING HVAC & CONTROLS PENETRATIONS @ 3 HOUR SECOND FLOOR DECK
03/25/2008 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
MUST COMPLETE FIRE CAULK FROM TOP AND BOTTOM OF PENETRATION AT SAME TIME
03/24/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
HVAC & PLUMBING PENETRATIONS THRU SECOND FLOOR DECK
02/05/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
MONO-COAT FIREPROOFING @ UNDERSIDE MEZZ. STRUCTURAL MEMBERS