Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM00014

Parcel: 137055070

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM00014

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/25/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
RTU-12 OK
DUCT SMOKE DETECTOR TEST OK
IT IS MY UNDERSTANDING THAT CHANGES HAVE BEEN MADE TO THE RTU-1O SYSTEM, THIS ALONG WITH EF-5 WILL BE BALANCED AT A LATER DATE. NO LIFE SAFETY ISSUES WERE OBSERVED. SEE BUILDING INSPECTOR FOR TEMP C OF O
07/21/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
RTU 10 - NO DATA
EF-5 NO DATA
RTU-12 30% LOW ON OUTSIDE AIR
PROVIDE DUCT SMOKE DETECTOR TEST DATA