Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/25/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* RTU-12 OK DUCT SMOKE DETECTOR TEST OK IT IS MY UNDERSTANDING THAT CHANGES HAVE BEEN MADE TO THE RTU-1O SYSTEM, THIS ALONG WITH EF-5 WILL BE BALANCED AT A LATER DATE. NO LIFE SAFETY ISSUES WERE OBSERVED. SEE BUILDING INSPECTOR FOR TEMP C OF O |
|
| 07/21/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* RTU 10 - NO DATA EF-5 NO DATA RTU-12 30% LOW ON OUTSIDE AIR PROVIDE DUCT SMOKE DETECTOR TEST DATA |