Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM00014
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/05/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* GRID LINES F TO K SALES FLOOR OK TO TILE SALON AND PORTRAIT STUDIO OK TO TILE |
|
06/03/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RESTROOMS & OFFICES OK TO TILE |
|
05/30/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
05/23/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSULATION STILL NOT FINISHED 2. NO SAFETY WIRES ON REGISTERS ALL FUTURE FAILED INSPECTIONS WILL REQUIRE A REFEE |
|
05/21/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
04/29/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO PROCEED DUCT GAUGES CORRECTED |
|
04/23/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO PROCEED WITH DUCT WRAP ANGLE IRON ON SUPPLY AND RETURN DROPS OK DUCT SMOKE DETECTORS SAMPLE TUBES OK |
|
04/15/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |