Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00014
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* COMPLETE SPEAKER INSTALL |
|
06/27/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT M/C CABLE WITHIN 12" OF BOXES FOR OUTLETS NO ONE ON SITE FINISH JEWELRY |
|
06/13/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK RESTROOMS & ZONE 4 |
|
06/12/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ZONE 1 |
|
06/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. MC CABLE TO BE SUPPORTED WITHIN 12" AND AT 6' INTERVALS, MC NOT TO LAY ON GRID FOR CEILING 2. WIRES USED FOR SUPPORT TO BE TIED ON EACH END 3. CONDUIT TO BE SUPPORTED WITHIN 3' OF BOX OR 5' PER EXCEPTION 4. LV CABLING TO BE SUPPORTED 5. OK PORTRAIT STUDIO 6. REMOVE TEMP LTG. WHEN NOT NEEDED |
|
06/09/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING NORTH OF COL. "F" |
|
06/06/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SEISMIC REQUIRED FOR EXIT LIGHTS IN GRID |
|
05/21/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
05/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/10/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |