Permit: T07CM00014

Parcel: 137055070

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00014

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/01/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
COMPLETE SPEAKER INSTALL
06/27/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT M/C CABLE WITHIN 12" OF BOXES FOR OUTLETS

NO ONE ON SITE FINISH JEWELRY
06/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK RESTROOMS & ZONE 4
06/12/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ZONE 1
06/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. MC CABLE TO BE SUPPORTED WITHIN 12" AND AT 6' INTERVALS, MC NOT TO LAY ON GRID FOR CEILING
2. WIRES USED FOR SUPPORT TO BE TIED ON EACH END
3. CONDUIT TO BE SUPPORTED WITHIN 3' OF BOX OR 5' PER EXCEPTION
4. LV CABLING TO BE SUPPORTED
5. OK PORTRAIT STUDIO
6. REMOVE TEMP LTG. WHEN NOT NEEDED
06/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING NORTH OF COL. "F"
06/06/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
SEISMIC REQUIRED FOR EXIT LIGHTS IN GRID
05/21/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/16/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/10/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*