Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00006
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2007 | ELECTRIC - FINAL | Approved | ||
04/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SEISMIC WIRES ON EXITS THAT WERE ADDED 2. ONE EXIT ON SWITCH LEG NEEDS TO BE ON CONSTANT POWER 3. NEW EXITS NOT LIGHTING ON LOSS OF POWER 4. QUAD RECEPTACLE MISSING WALL PLATE 5. BLANK UNUSED OUTLET LOCATIONS OR INSTALL VOICE DATA CABLE. |
|
04/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL EM LIGHTING PER APPROVED PLANS 2. NO POWER TO LARGE NUMBER OF RECEPTACLES 3. INSTALL EXIT LIGHTS PER APPROVED PLANS 4. NOT A COMPLETE FINAL INSPECTION |