Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00006

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2007 ELECTRIC - FINAL Approved
04/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SEISMIC WIRES ON EXITS THAT WERE ADDED
2. ONE EXIT ON SWITCH LEG NEEDS TO BE ON CONSTANT POWER
3. NEW EXITS NOT LIGHTING ON LOSS OF POWER
4. QUAD RECEPTACLE MISSING WALL PLATE
5. BLANK UNUSED OUTLET LOCATIONS OR INSTALL VOICE DATA CABLE.
04/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL EM LIGHTING PER APPROVED PLANS
2. NO POWER TO LARGE NUMBER OF RECEPTACLES
3. INSTALL EXIT LIGHTS PER APPROVED PLANS
4. NOT A COMPLETE FINAL INSPECTION