Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00006

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2007 ELECTRIC - ABOVE CEILING Approved
04/27/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/26/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/24/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/20/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OPEN TILE TO ACCESS AREAS TO INSPECT - SMALL ROOMS
2. FINISH PREVIOUS ITEM WITH REGARD TO VDV CABLING

OK POWER POLES
04/18/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SECURE CABLES UPON EXITING CABLE TRAY
2. SUPPORT FLEX CONDUIT AS PER CODE
3. NOTE THE USE OF MULTI-WIRE BRANCH CIRCUITS 210.4
04/10/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED
04/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABLING TO BE INDEPENDENTLY SUPPORTED 300.11 ALSO, AS PER 725.3 & 6, 760.3 & 6, 800.3 & 6
2. PLEASE VERIFY PLENUM RATING ON ALL VDV CABLING
3. FINISH CONNECTIONS OF POWER POLES

OK LIGHT FIXTURES.
03/27/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/26/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/23/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*